Compressed Air

Here at the Titus Company we think of compressed air as the fourth utility and so strive to make your compressed air system as reliable as your electrical, water and steam supplies. What can make this challenging is knowing what the true needs of the system are now and in the future. A very simple mistake in sizing, type, placement of the equipment or future requirements can be very costly in the short term and into the future. The following is a very simple explanation of what a compressed air system does.

There are 5 main things the system needs to be doing at all times:
  • Compressing The Air
  • Cooling The Air
  • Cleaning The Air
  • Drying The Air
  • Delivering The Air

Compressing the Air

Oil flooded rotary screw compressors are the primary compressor of choice these days and fully 95% of them are air cooled. While these machines are relatively simple to understand and operate, how the machines are controlled(i.e. variable speed, on/off, load/unload, modulated or other) is very important to understand. Will there be multiple compressors, and, if so, how will the machines interact to provide compressed air energy as efficiently and reliably as possible. Will your production stop if the primary compressor goes down, and, if so, should a backup compressor also be considered? Also important to consider is how much air is required by the plant now and in the future.

Where to install the compressed air equipment is another important consideration. By their nature, compressors create a lot of heat and need a considerable amount of clean, cool air to operate well. They are also better installed out of the weather and protected from the elements. Rotary screw compressors will have oil and air outlet temperatures in the 200 °F range. A typical 50 HP compressor will require approximately 4,000 CFM of cooling air supplied from an internal fan, and with a fresh air room requirement of 8,000 CFM. The fresh-air room requirement is generally the customer’s responsibility and in most cases requires an exhaust fan. The exhaust fan should be temperature controlled. As with all rotating equipment, the cooler the running temperature, the longer the operating life will generally be . This cooling will have an impact on the quality of the air the compressor delivers to the compressed air treatment equipment. Most compressors have a filtration system for the cooling air before it enters the air cooled heat exchangers. The cooling air should be as dust free as possible.

The heat generated by the compressor can be recaptured and ducted into a space that requires heat or can be recaptured by using a compressor that is water cooled. The heat generated is considerable and should not be wasted if at all possible.

The quality of the compressed air supplied to the plant starts at the compressor intake filter. So whatever is in the air where the compressor is installed will get into your compressed air. If it is not possible to install the compressor in an area that is free from chemicals, dust or anything else you don’t want in your compressed air, then moving the compressor intake filter location should be a serious consideration.

Basically, what happens in a compressor is that it sucks in a cubic foot, 1728 cubic inches (12 x 12 x 12 inches) of clean cool air and turns it into a hot, oily, water-saturated cube that is now approximately 222 cubic inches in volume and is 6 x 6 x 6 inches in size. You now have a lot of potential energy because those 222 cubic inches would really like to be 1728 cubic inches in size again. Thus ends the compression phase of the process. Now this hot, oily, water-saturated air has to be cooled, cleaned, dried and delivered to where you want to use it. The compressor still has some work to do though. The first thing the compressor needs to do is get back as much oil as it can from the compressed air. This is generally done with a air/oil separator. This separator is specifically designed to remove the oil from the compressed air. Some of the compressor oil will make it out with the air. Typical ratings for rotary screw compressor oil discharge are in the ppm range, but if the separator is not properly maintained, oil discharge levels can be measured in gallons. Gallons of compressor oil in the downstream air treatment equipment or your process equipment is generally not a good thing.

Cooling The Compressed Air

The 4,000 CFM of cooling air now has to do its job. The 4,000 CFM of air is forced through the compressor after-cooler by a fan. Generally, these after-coolers arepart of the compressor package but can be installed as a stand-alone unit. These after-coolers look very similar to the radiator on your car. They have relatively small openings and these openings can get clogged. When they do, the effectiveness of the radiator (after-cooler) is reduced. The compressed air is passing through the tubes and the cooling air is flowing past the tubes and between the cooling fins and removing the heat from the compressed air. Generally, these coolers have two sections. One section is cooling the air and the other section is used to cool the oil.

As the air is compressed it gets hotter. We call this the "heat of compression” and that temperature rise gives the air a higher capacity to hold water. Now, we want to remove that heat, and once that process begins, the water will condense and go back to its liquid form.

Let’s talk about water for a moment. The air the compressor sucked in had some water in it and generally we measure that by using relative humidity. From here on out we will talk about dew point as a measurement of the water content of the compressed air. But let’s first figure out how much water we are talking about. We will assume that the air coming out of the compressor is saturated and this will be the case unless the relative humidity of the air the compressor is sucking in is very low.

If you have one 50 HP compressor delivering 225 SCFM of compressed air at 100 PSIG and 100°F and do nothing with that air after cooling it to 100°F you will put approximately 5 gallons of water into your compressed air system every 8 hours. Let’s say your after-cooler is not performing and the outlet temperature goes from 100°F to 120°. Then the amount of water going into the system will be approximately 9 gallons of water in an 8 hour period. Now, you may never see all of this water but if the compressed air is cooling as it travels in the piping network or whenever the pressure is reduced, then you will see the water. Bottom line you should take care to make sure you have adequate cooling for the compressor and related equipment.

The first step in removing this water is a air/moisture separator designed to remove the liquid water from the compressed air. This separator is generally installed at the outlet of the compressor and should have an automatic condensate trap to dispel the water from the separator. We will talk about condensate drains in a little while.

At this point in the process we now have cool (100°F), wet, compressed air with a dew point of 100°F. The air remains saturated. Let’s talk a little bit about dew point (DP). Dew point, like relative humidity (RH), is a measurement of the amount of water in air, but, unlike RH, it is not relative to the temperature of the air. In all of our discussions the DP we are talking about is DP at pressure. You should be very careful when selecting compressed air treatment products because some manufactures will quote based on atmospheric DP. For example if the dew point of the air you were sucking into the compressor had a DP of -40°F after you compressed it to 100 PSIG, the DP would be -4°F.

Dew point is basically the temperature point where the air will not hold any more water. So, if you had air at a dew point of 100°F and you raised the temperature of the air to 120°F, the dew point would still be 100°F. Now let’s say you lowered the temperature of the air to 90°F. What you have done is lowered the air’s ability to hold water, so the water condenses out of the air in the form of liquid. If you could remove all of the liquid water that has condensed out the dew point of the air would now be 90°F.

Cleaning The Air

So, now we have compressed the air to 100 PSIG, cooled it to 100°F and removed the bulk liquid water. The air is now usable, but for 99% of the applications we work on, this air still needs some work. This is where we would apply compressed air treatment products. The first step in this part of the process is filtration. Filtration costs money beyond just the replacement cost of the elements. The additional costs come into play because most filtration products need velocity across a filter media to work properly, and this causes pressure drop. How this will increase your costs is simple. You paid the power company for the electricity to compress the air to 100 PSIG and now after the filtration process you may only have – let’s say – 95 PSIG. The compressor may need to come on more often or stay on longer to maintain system pressure at the set-point required for your system. For this reason it is important to reduce system pressure drop whenever and wherever possible.

The primary goal of the filtration process is to remove solid particulate contaminants, liquid water, and oil. The solid particulate removal is relatively straight-forward. With the filter media you create a path for the air to travel through that blocks everything above a given micron size. Typically today when we are talking about filtration we are talking about particle sizes in the 1 to 0.01 micron range for pre-filters (particulate or coalescing) and 5 to 10 microns for after-filters (particulate). So how big is a micron?
  • In one inch there are 25,400 microns
  • One micron is 0.00004 inches
  • Most people can see something that is 40 microns
  • A white blood cell is about 25 microns
So, the filters in today’s systems are capturing very small particles. The reason for this in a pre-filter is to keep liquid water and/or oil out of the treatment equipment and/or your processes. The filters we use to do this are called coalescing- type filters and the 1 micron filter is typically in place to protect the 0.01 micron filter. The liquid water you will see draining out of the filter bowls has been coalesced from water droplets too small to even see in some cases. There are some very complicated processes taking place in the filter media to make them work. You will hear people talk about Brownian Movement, Inertial Impaction or Direct Interception. Bottom line, coalescing filters work on the basic principle that if you force two, 0.01 micron sized drops of liquid into an opening (filter media), at the same time, that is only 0.01 microns in size, the two water droplets will be too large to make it through and they will join (coalesce) with other droplets of liquid and eventually drain down the filter element into the bottom of the filter bowl. Once this water and oil mixture has collected in the bottom of the filter bowl, it will be discharged by the condensate drain traps. You can imagine that any significant amount of dirt that may make its way into the filter media will cause a higher pressure drop. So while most filters of this type will start out with a pressure drop in the 2 to 3 PSID (Pounds Per Square Inch Drop) range that pressure drop number can go up significantly. The selection of these filters is a very important part of the compressed air system. If the filter is too small, you will have increased your pressure drop and perhaps reduced its performance. A filter bowl that is too small may cause the velocity in the filter bowl to be so high that it picks the water off of the drain layer of the filter element and carries it down stream (generally referred to as re-entrainment). Pick a filter that is too big and you have reduced your pressure drop, but perhaps also reduced the coalescing action, because the velocity across the filter media is so low it will not force the small droplets of water or oil together.

You will hear claims that this filter or that filter will remove 99.9% of the water or oil in a compressed air stream and while this may be true, remember it is 99.9% of the water and oil that is in a liquid form.

After-filters are used to collect solid particulates from the air stream, these filters range in micron size from 1 to 10 microns. Some can be custom designed for various temperatures and micron rating.

Drying The Air

The general category for all this equipment is called compressed air treatment products, which may also include filtration, but for our discussion and this section we will just consider dryers. There are basically three ways to dry compressed air; refrigeration, membrane and desiccant dryers. But first let’s talk about dew point. The following is the definition from Wikipedia, the free encyclopedia: The dew point is the temperature to which a given parcel of air must be cooled, at constant barometric pressure, for water vapor to condense into water. The condensed water is called dew. The dew point is a saturation point. When the dew point temperature falls below freezing it is often called the frost point, as the water vapor no longer creates dew but instead creates frost or hoarfrost by deposition. The dew point is associated with relative humidity. A high relative humidity indicates that the dew point is closer to the current air temperature. Relative humidity of 100% indicates the dew point is equal to the current temperature and the air is maximally saturated with water. When the dew point remains constant and temperature increases, relative humidity will decrease.
When you purchase a dryer, the first question you need to answer is, "at what dew point does the compressed air in my system need to be?” This may be dependant on various processes or just dry enough to keep the water out of your compressed air.


Mailing Address:

36 Mountain View Road
Morgantown, PA 19543

Telephone/Fax:

Tel: 610.913.9100
Fax: 610.913.9200

E-mail:

sales@titusco.com
service@titusco.com

TN2 Generators:

www.tn2generators.com
info@tn2generators.com