Neutronics Air Compression System Monitoring Equipment
Neutronics 1000 Series
The Model 1100 is a compact analyzer for oxygen gas measurement and process control applications. Designed for a measurement range of zero to 100% oxygen, the system features a reliable electrochemical sensor that can be remote mounted at the sampling point to ensure a fast response time. A flow-through mounting head allows the sensor to be horizontally or vertically mounted directly into the sampled process gas stream.
Specifications:
- Sensor: EC250 (CAG-250E) electrochemical cell (alternate sensors available upon request)
- Measurement Range: 0-1%, 0-10%, 0-25%, 0-50%, 0-100%, auto-ranging or fixed range
- Display: 0.75” (19.05mm) LED digital display with color coded LEDs for system status — Alarms 1&2= RED, system fault= YELLOW, OK and online= GREEN
- Response Time: T90 < 20 seconds
- Operating Temperature (sensor): 5 to 40º C
- Operating Temperature (analyzer): 0 to 65º C
- Sample pressure: 1 to 3 psig nominal, 7 psig maximum
- Serial service port: RS-232
- Analog Voltage Output: choice of 0-1VDC, 0-5VDC or 0-10VDC
- Analog Current Output: 4-20mA, 12VDC, powered by the analyzer
- Relay Outputs: Two alarms with adjustable form C relay outputs (configurable for fail-safe/non-fail-safe and ascending/descending action); one system fault relay
- Power: 90-264VAC, 47-63 Hz, single phase or 18-30VDC
- Environmental Ratings: Faceplate — NEMA 4, IP66; electronic compartment — NEMA 1, IP20
- Weight: 2lb. (0.9kg)
Features:
- 0 to 100% measurement range
- Remote mounted electrochemical sensor
- Auto-range or fixed range O2 measurement
- Two adjustable alarms with configurable relay outputs
- Fast single-gas or two-gas calibration
Neutronics 7100 Series
The Neutronics Model 7100 is a compact analyzer designed for trace oxygen gas measurement. This analyzer features a rapid-response mini-zirconia sensor with a measurement range of 0 to 1000 ppm oxygen. Extremely fast response, high accuracy, and no requirement for periodic calibrations make this analyzer a low-maintenance solution that delivers reliable performance for critical process control applications.
Specifications:
- Sensor: Mini-Zirconia Sensor, ZR-400
- Measurement Range: 0-1,000ppm auto-range or fixed range output (0-100 ppm, 0-1,000 ppm)
- Display: 0.75” (19.05mm) LED digital display; color coded LEDs for system status — Alarms 1&2= RED, system fault= YELLOW, OK and online= GREEN
- Response Time: T90
- Accuracy: ±2.0% of range at calibrated temperature and pressure of ±3ppm
- Operating Temperature: 0-50º C (32-122º F)
- Sample Pressure: 15 inHg vacuum to 7 psig (0.5 to 1.5 bar)
- Serial Service Port: RS-232
- Analog Voltage Output: Choice of 0-1VDC, 0-5VDC, or 0-10VDC
- Analog Current Output: 4-20mA, 12VDC, negative ground
- Alarm Outputs: Two alarms with adjustable form C relay outputs; configurable for fail-safe/non-fail-safe and ascending/descending action
- Power: 90-264 VAC, 50-60 Hz, single phase or 24 VDC
- Environmental Ratings (Analyzer): faceplate — NEMA 4, IP66; electronics compartment — NEMA 1, IP20
- Weight: 3 lbs. (1.4 kg)
Features:
- 0 to 1000 ppm measurement range
- Mini-zirconia oxide ZR400 sensor
- ±2.0% accuracy
- Internal or external remote sensor mounting with KF fitting option
- T90< 10 seconds